Attribute VB_Name = "Converter_rRou2C"
Function tConverterRoughness(rRou_or_C As Double, ConvertDir As String) As Double
' BiDirectional convertor tool for pipe roughness as 'e/D to C' or 'C to e/D' - rRou is relative roughness (e/D)
' based on data given by Diskin,M.H. - The limits of applicability of the Hazen-Williams formula
' The data by Diskin can be found in the Excel sheet "zDiskinData"
' by Tol,Hakan Ibrahim from the PhD study at Technical University of Denmark
' PhD Topic: District Heating in Areas with Low-Energy Houses
' WARNING: This VBA code uses Diskin Data ranges named as "rRou_Data" and "Cmod_Data" given in sheet "zDiskinData"
' DESRIPTION
' INPUTS
' rRou_C : Relative roughness (eps/D) or roughness coefficient (C), used respectively in Darcy-Weisbach (DW) or Hazen-Williams (HW) formulations
' Depends on the user choice of the conversion direction
' ConvertDir : Direction for conversion, as either 'rRou2C' for 'e/D to C' or 'C2rRou for 'C to e/D'
' OUTPUT
' tConverterRoughness: Roughness coefficient (C) for HW or relative roughness (eps/D) for DW depending on the convert direction selected
' Calculations as to the Direction of Conversion given as input 'rRou2C' or 'C2rRou'
Select Case ConvertDir
Case "rRou2C" ' C as a function of relative roughness rRou
tConverterRoughness = -147.120418481659 * rRou_or_C ^ 0.168899561932556 + 179.126967041124
Case "C2rRou" ' rRou as a function of C
tConverterRoughness = Linterp(Range("rRou_Data"), Range("Cmod_Data"), rRou_or_C)
Case Else
MsgBox "You must choose either -rRou2C- or -C2rRou- to indicate convert direction"
End Select
End Function