Notifications
You must be signed in to change notification settings - Fork 3
/
check_apc_pdu.sh
executable file
·233 lines (194 loc) · 10.1 KB
/
check_apc_pdu.sh
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
143
144
145
146
147
148
149
150
151
152
153
154
155
156
157
158
159
160
161
162
163
164
165
166
167
168
169
170
171
172
173
174
175
176
177
178
179
180
181
182
183
184
185
186
187
188
189
190
191
192
193
194
195
196
197
198
199
200
201
202
203
204
205
206
207
208
209
210
211
212
213
214
215
216
217
218
219
220
221
222
223
224
225
226
227
228
229
230
231
#!/bin/bash
# Rewritten by Gerrit Doornenbal
# Based on script from Andrew Singer (https://www.rainsbrook.co.uk/wiki/doku.php/nagios/check_apcpowerstrip)
#
# note: AP8XXX measurements below 0.5A are squelched to 0A...
#
# v0.1 nov 2019
# * changed to named options intead of only options
# * added new PDU type.
# * added debug option
# * added statistics output
# * output/return codes tuned
# *
#
# Request:
# This script is tested on the PDU stated in the help section, but should work with
# other types to. Please let me know if this script works on other models, so i can
# expland this list. (g.doornenbal AT gmail.com), or
#
#Originally written Andrew Stringer, 31/10/2013
#Purpose is to test power usage on smart power strips
#See http://www.oidview.com/mibs/318/PowerNet-MIB.html
#OID's of use for multi bank PDU
#.1.3.6.1.4.1.318.1.1.12.2.3.1.1.2.1 <- Multi-Bank Total Load (divide by 10)
#.1.3.6.1.4.1.318.1.1.12.2.3.1.1.2.2 <- Multi-Bank B1 Load (divide by 10)
#.1.3.6.1.4.1.318.1.1.12.2.3.1.1.2.3 <- Multi-Bank B2 Load (divide by 10)
#.1.3.6.1.4.1.318.1.1.12.2.4.1.1.2.1 <- Multi-Bank B1 Low Load Warning Threshold
#.1.3.6.1.4.1.318.1.1.12.2.4.1.1.2.2 <- Multi-Bank B2 Low Load Warning Threshold
#.1.3.6.1.4.1.318.1.1.12.2.2.1.1.2.1 <- Multi-Bank Total Low Load Warning Threshold
#.1.3.6.1.4.1.318.1.1.12.2.4.1.1.3.1 <- Multi-Bank B1 Near Overload Warning Threshold
#.1.3.6.1.4.1.318.1.1.12.2.4.1.1.3.2 <- Multi-Bank B2 Near Overload Warning Threshold
#.1.3.6.1.4.1.318.1.1.12.2.2.1.1.3.1 <- Multi-Bank Total Near Overload Warning Threshold
#.1.3.6.1.4.1.318.1.1.12.2.4.1.1.4.1 <- Multi-Bank B1 Overload Alarm Threshold
#.1.3.6.1.4.1.318.1.1.12.2.4.1.1.4.2 <- Multi-Bank B2 Overload Alarm Threshold
#.1.3.6.1.4.1.318.1.1.12.2.2.1.1.4.1 <- Multi-Bank Total Overload Alarm Threshold
#Single Bank OID
#.1.3.6.1.4.1.318.1.1.12.2.3.1.1.2.1 <- Single-Bank Total Load (divide by 10)
#.1.3.6.1.4.1.318.1.1.12.2.2.1.1.2.1 <- Single-Bank Low Load Warning Threshold
#.1.3.6.1.4.1.318.1.1.12.2.2.1.1.3.1 <- Single-Bank Near Overload Warning Threshold
#.1.3.6.1.4.1.318.1.1.12.2.2.1.1.4.1 <- Single-Bank Overload Alarm Threshold
#.1.3.6.1.4.1.318.1.1.12.1.5.0 = PDU Model number, dual AP8953, single AP7954
PROGNAME=`basename $0`
version="version 0.1"
debug=0
SINGLEBANK="AP7951,AP7954"
DUALBANK="AP7922,AP8953,AP8853"
nagios_status=0
nagios_states=(OK WARNING CRITICAL UNKNOWN)
nagios_message=""
statistics="|" # format: 'label'=value[UOM];[warn];[crit];[min];[max]
stats=0;
BANK=T #Default total only
squelched="squelched to"
#Print out command line options
usage() {
echo "Usage: $PROGNAME -H <hostname> -C <communitystring> "
echo
echo "Plugin to read the power load from network connected APC PDU's."
echo "This plugin reads the system-name and the Warning/Critical tresholds from the PDU."
echo "So you should set these settings in the (web)GUI of the PDU."
echo "There different PDU types, some with multiple internal power distrubition banks."
echo "This plugin can read these banks separately with the -B (Bank) option as stated below:"
echo " -B <T/B1/B1/A>"
echo " Default = T(otal), option A(ll) gives all Banks + Total."
echo
echo "Other (optional) options:"
echo " -f Give also statistic info."
echo " -V Version of this plugin."
echo " -d Debug, show extra info."
echo " -h or -? This help message."
echo
echo "This plugin should work on many PDU models, but is tested on the following PDU's:"
echo " AP7951,AP7954,AP7922,AP8953,AP8853"
exit 1;
}
while getopts C:H:B:dhfV? options;
do
case $options in
C ) COMMSTRING="$OPTARG";;
H ) HOSTNAME="$OPTARG";;
B ) BANK="$OPTARG";;
d ) debug=1;;
f ) stats=1;;
V ) echo "${0##*/} $version"
exit 1;;
? ) usage;;
h ) usage;;
esac
done
if [ "$COMMSTRING" == "" ] || [ "$HOSTNAME" == "" ]; then
usage
fi
SNMPGET=/usr/bin/snmpget
MODEL=`${SNMPGET} -v1 -c ${COMMSTRING} ${HOSTNAME} SNMPv2-SMI::enterprises.318.1.1.12.1.5.0 | cut -d: -f4 | cut -d" " -f2 | sed 's/^\"\(.*\)\"$/\1/' `
NAME=`${SNMPGET} -v1 -c ${COMMSTRING} ${HOSTNAME} SNMPv2-MIB::sysName.0 | cut -d: -f4 | cut -d" " -f2 | sed 's/^\"\(.*\)\"$/\1/' `
#SNMPv2-MIB::sysName.0
if [ $debug = 1 ]; then echo "Model PDU found is: ${MODEL} Name:$NAME";echo; fi
nagios_message="${NAME}:"
if [ -z "${MODEL}" ]; then
echo "UNKNOWN - An error has occurred communicating with the PDU."
exit 3
fi
# First do the total load (is the same for SINGLE and DUAL bank PDU's!
if [[ "TA" == *"${BANK}"* ]]
then
TOTALLOADRAW=`${SNMPGET} -v1 -c ${COMMSTRING} ${HOSTNAME} SNMPv2-SMI::enterprises.318.1.1.12.2.3.1.1.2.1 | cut -d: -f4 | cut -d" " -f2 `
TOTALLOAD=`echo "scale = 2; $TOTALLOADRAW / 10" | bc -l`
WARNINGTHRESHOLD=`${SNMPGET} -v1 -c ${COMMSTRING} ${HOSTNAME} SNMPv2-SMI::enterprises.318.1.1.12.2.2.1.1.3.1 | cut -d: -f4 | cut -d" " -f2 `
CRITICALTHRESHOLD=`${SNMPGET} -v1 -c ${COMMSTRING} ${HOSTNAME} SNMPv2-SMI::enterprises.318.1.1.12.2.2.1.1.4.1 | cut -d: -f4 | cut -d" " -f2 `
TOTALMAXLOAD=`${SNMPGET} -v1 -c ${COMMSTRING} ${HOSTNAME} SNMPv2-SMI::enterprises.318.1.1.12.2.1.3.0 | cut -d: -f4 | cut -d" " -f2 `
statistics="$statistics 'TOTAL'=$TOTALLOAD;$WARNINGTHRESHOLD;$CRITICALTHRESHOLD;0;$TOTALMAXLOAD"
if [ $TOTALLOAD == 0 ] && [[ "${MODEL}" == "AP8"* ]]; then TOTALLOAD="$squelched 0"; fi
if [ $debug = 1 ]; then echo "TOTAL load=${TOTALLOAD}A (raw:${TOTALLOADRAW}), w=${WARNINGTHRESHOLD}, c=${CRITICALTHRESHOLD} "; fi
if [[ "$TOTALLOADRAW" -lt $(($WARNINGTHRESHOLD * 10)) ]]; then
nagios_message="$nagios_message Total Load:${TOTALLOAD}A."
elif [[ "$TOTALLOADRAW" -le $(($CRITICALTHRESHOLD * 10 )) ]]; then
nagios_message="$nagios_message Total Load:${TOTALLOAD}A, warning:${WARNINGTHRESHOLD}A."
nagios_status=1
elif [[ "$TOTALLOADRAW" -ge $(($CRITICALTHRESHOLD * 10 )) ]]; then
nagios_message="$nagios_message Total Load:${TOTALLOAD}A, critical:${CRITICALTHRESHOLD}A."
nagios_status=2
else
nagios_message="$nagios_message Total Load:unknown."
nagios_status=3
fi
fi
if [[ "$SINGLEBANK" == *"${MODEL}"* ]]
then
TYPE='SINGLEBANK'
fi
if [[ "$DUALBANK" == *"${MODEL}"* ]]
then
TYPE='DUALBANK'
case ${BANK} in
B1|b1|A)
#Bank B1 load
BANK1LOADRAW=`${SNMPGET} -v1 -c ${COMMSTRING} ${HOSTNAME} SNMPv2-SMI::enterprises.318.1.1.12.2.3.1.1.2.2 | cut -d: -f4 | cut -d" " -f2 `
BANK1LOAD=`echo "scale = 2; $BANK1LOADRAW / 10" | bc -l`
B1WARNINGTHRESHOLD=`${SNMPGET} -v1 -c ${COMMSTRING} ${HOSTNAME} SNMPv2-SMI::enterprises.318.1.1.12.2.4.1.1.3.1 | cut -d: -f4 | cut -d" " -f2 `
B1CRITICALTHRESHOLD=`${SNMPGET} -v1 -c ${COMMSTRING} ${HOSTNAME} SNMPv2-SMI::enterprises.318.1.1.12.2.4.1.1.4.1 | cut -d: -f4 | cut -d" " -f2 `
B1MAXLOAD=`${SNMPGET} -v1 -c ${COMMSTRING} ${HOSTNAME} SNMPv2-SMI::enterprises.318.1.1.12.2.1.6.1.3.1 | cut -d: -f4 | cut -d" " -f2 `
statistics="$statistics 'BANK1'=$BANK1LOAD;$B1WARNINGTHRESHOLD;$B1CRITICALTHRESHOLD;0;$B1MAXLOAD"
if [ $BANK1LOAD == 0 ] && [[ "${MODEL}" == "AP8"* ]]; then BANK1LOAD="$squelched 0"; fi
if [ $debug = 1 ]; then echo "BANK1 load=${BANK1LOAD}A (raw:${BANK1LOADRAW}), w=${B1WARNINGTHRESHOLD}, c=${B1CRITICALTHRESHOLD} "; fi
if [[ "$BANK1LOADRAW" -lt $(($B1WARNINGTHRESHOLD * 10)) ]]; then
nagios_message="$nagios_message Bank B1 load: ${BANK1LOAD}A."
elif [[ "$BANK1LOADRAW" -le $(($B1CRITICALTHRESHOLD * 10 )) ]]; then
nagios_message="$nagios_message Bank B1 load: ${BANK1LOAD}A, warning:${B1WARNINGTHRESHOLD}A."
nagios_status=1
elif [[ "$BANK1LOADRAW" -ge $(($B1CRITICALTHRESHOLD * 10 )) ]]; then
nagios_message="$nagios_message Bank B1 load: ${BANK1LOAD}A, critical:${B1CRITICALTHRESHOLD}A."
nagios_status=2
else
nagios_message="$nagios_message Bank B1 load: unknown."
nagios_status=3
fi
#end of bank B1 case
;;&
B2|b2|A)
#Bank B2 load
BANK2LOADRAW=`${SNMPGET} -v1 -c ${COMMSTRING} ${HOSTNAME} SNMPv2-SMI::enterprises.318.1.1.12.2.3.1.1.2.3 | cut -d: -f4 | cut -d" " -f2 `
BANK2LOAD=`echo "scale = 2; $BANK2LOADRAW / 10" | bc -l`
B2WARNINGTHRESHOLD=`${SNMPGET} -v1 -c ${COMMSTRING} ${HOSTNAME} SNMPv2-SMI::enterprises.318.1.1.12.2.4.1.1.3.2 | cut -d: -f4 | cut -d" " -f2 `
B2CRITICALTHRESHOLD=`${SNMPGET} -v1 -c ${COMMSTRING} ${HOSTNAME} SNMPv2-SMI::enterprises.318.1.1.12.2.4.1.1.4.2 | cut -d: -f4 | cut -d" " -f2 `
B2MAXLOAD=`${SNMPGET} -v1 -c ${COMMSTRING} ${HOSTNAME} SNMPv2-SMI::enterprises.318.1.1.12.2.1.6.1.3.2 | cut -d: -f4 | cut -d" " -f2 `
statistics="$statistics 'BANK2'=$BANK2LOAD;$B2WARNINGTHRESHOLD;$B2CRITICALTHRESHOLD;0;$B2MAXLOAD"
if [ $BANK2LOAD == 0 ] && [[ "${MODEL}" == "AP8"* ]]; then BANK2LOAD="$squelched 0"; fi
if [ $debug = 1 ]; then echo "BANK2 load=${BANK2LOAD}A (raw:${BANK2LOADRAW}), w=${B2WARNINGTHRESHOLD}, c=${B2CRITICALTHRESHOLD} "; fi
if [[ "$BANK2LOADRAW" -lt $(($B2WARNINGTHRESHOLD * 10)) ]]; then
nagios_message="$nagios_message Bank B2 load:${BANK2LOAD}A."
elif [[ "$BANK2LOADRAW" -le $(($B2CRITICALTHRESHOLD * 10 )) ]]; then
nagios_message="$nagios_message Bank B2 load:${BANK2LOAD}A, warning:${B2WARNINGTHRESHOLD}A."
nagios_status=1
elif [[ "$BANK2LOADRAW" -ge $(($B2CRITICALTHRESHOLD * 10 )) ]]; then
nagios_message="$nagios_message Bank B2 load:${BANK2LOAD}A, critical:${B2CRITICALTHRESHOLD}A."
nagios_status=2
else
nagios_message="$nagios_message Bank B2 load: unknown."
nagios_status=3
fi
#end of bank B2 case
;;&
esac
else
nagios_message="$nagios_message No Match for PDU model ${MODEL} found."
TYPE='UNKNOWN'
nagios_status=3
fi
if [ $debug = 1 ]; then echo "PDU type is: ${TYPE}"; fi
if [ $stats = 1 ]; then
nagios_message="$nagios_message $statistics"
fi
echo "${nagios_states[$nagios_status]}: $nagios_message"
exit $nagios_status