Arista7050cx3 TD3 SKU changes for pg headroom value after interop testing w/ 8102 #11901
Merged
lguohan
merged 1 commit into
sonic-net:master
from
developfast:arista7050cx3-headroom-update
Aug 31, 2022
Merged
Arista7050cx3 TD3 SKU changes for pg headroom value after interop testing w/ 8102 #11901
lguohan
merged 1 commit into
sonic-net:master
from
developfast:arista7050cx3-headroom-update
Aug 31, 2022
Conversation
This file contains bidirectional Unicode text that may be interpreted or compiled differently than what appears below. To review, open the file in an editor that reveals hidden Unicode characters.
Learn more about bidirectional Unicode characters
…ting with cisco 8102 Signed-off-by: dojha <devojha@microsoft.com>
|
neethajohn
approved these changes
Aug 31, 2022
/azp run |
Commenter does not have sufficient privileges for PR 11901 in repo sonic-net/sonic-buildimage |
lguohan
pushed a commit
that referenced
this pull request
Aug 31, 2022
…esting with cisco 8102 (#11901) Why I did it After PFC interop testing between 8102 and 7050cx3, data packet losses were observed on the Rx ports of the 7050cx3 (inflow from 8102) during testing. This was primarily due to the slower response times to react to PFC pause packets for the 8102, when receiving such frames from neighboring devices. To solve for the packet drops, the 7050cx3 pg headroom size has to be increased to 160kB. How I did it Modified the xoff threshold value to 160kB in the pg_profile file to allow for the buffer manager to read that value when building the image, and configuring the device How to verify it run "mmuconfig -l" once image is built Signed-off-by: dojha <devojha@microsoft.com>
zbud-msft
pushed a commit
to zbud-msft/sonic-buildimage
that referenced
this pull request
Aug 31, 2022
…esting with cisco 8102 (sonic-net#11901) Why I did it After PFC interop testing between 8102 and 7050cx3, data packet losses were observed on the Rx ports of the 7050cx3 (inflow from 8102) during testing. This was primarily due to the slower response times to react to PFC pause packets for the 8102, when receiving such frames from neighboring devices. To solve for the packet drops, the 7050cx3 pg headroom size has to be increased to 160kB. How I did it Modified the xoff threshold value to 160kB in the pg_profile file to allow for the buffer manager to read that value when building the image, and configuring the device How to verify it run "mmuconfig -l" once image is built Signed-off-by: dojha <devojha@microsoft.com>
yxieca
pushed a commit
that referenced
this pull request
Sep 1, 2022
…esting with cisco 8102 (#11901) Why I did it After PFC interop testing between 8102 and 7050cx3, data packet losses were observed on the Rx ports of the 7050cx3 (inflow from 8102) during testing. This was primarily due to the slower response times to react to PFC pause packets for the 8102, when receiving such frames from neighboring devices. To solve for the packet drops, the 7050cx3 pg headroom size has to be increased to 160kB. How I did it Modified the xoff threshold value to 160kB in the pg_profile file to allow for the buffer manager to read that value when building the image, and configuring the device How to verify it run "mmuconfig -l" once image is built Signed-off-by: dojha <devojha@microsoft.com>
This commit could not be cleanly cherry-picked to 202012. Please submit another PR. |
zbud-msft
added a commit
to renukamanavalan/sonic-buildimage
that referenced
this pull request
Sep 12, 2022
* Add YANG models for structured events * [Arista] Update platform submodule (sonic-net#11853) * Advance submodule sonic-sairedis (sonic-net#11704) 2022-07-28 854d54e: Add support of mdio IPC server class using sai switch api and unix socket (sonic-net/sonic-sairedis#1080) (Jiahua Wang) 2022-07-27 513cb2a: [FlexCounter] Refactor FlexCounter class (sonic-net/sonic-sairedis#1073) (Junchao-Mellanox) * Update swss common submodule for events api (sonic-net#11858) #### Why I did it Structured events code like eventd, rsyslogplugin, requires changes made in swss-common Submodule adds these newest commits: 56b0f18 (HEAD, origin/master, origin/HEAD, master) Events: APIs to set/get global options (sonic-net#672) 5467c89 Add changes to yml file to improve pytest (sonic-net#674) #### How I did it Updated git submodule #### How to verify it Check new commit pointer * [Arista] Fix content of platform.json for DCS-720DT-48S (sonic-net#11855) Why I did it Content of platform.json was outdated and some platform_tests/api of sonic-mgmt were failing. How I did it Added the necessary values to platform.json How to verify it Running platform_tests/api of sonic-mgmt should yield 100% passrate. * [actions] Update github actions label and automerge. (sonic-net#11736) 1. Add auto approve step when adding label to version upgrading PR. 2. Use mssonicbld TOKEN to merge version upgrading PR instead of 'github actions' * [ci] Update reproducible build related pipeline. (sonic-net#11810) * Address Review Comment to define SONIC_GLOBAL_DB_CLI in gbsyncd.sh (sonic-net#11857) As part of PR sonic-net#11754 Change was added to use variable SONIC_DB_NS_CLI for namespace but that will not work since ./files/scripts/syncd_common.sh uses SONIC_DB_CLI. So revert back to use SONIC_DB_CLI and define new variable for SONIC_GLOBAL_DB_CLI for global/host db cli access Also fixed DB_CLI not working for namespace. * [Build] Increase the size of the installer image (sonic-net#11869) #### Why I did it Fix the build failure caused by the installer image size too small. The installer image is only used during the build, not impact the final images. See https://dev.azure.com/mssonic/build/_build/results?buildId=139926&view=logs&j=cef3d8a9-152e-5193-620b-567dc18af272&t=359769c4-8b5e-5976-a793-85da132e0a6f ``` + fallocate -l 2048M ./sonic-installer.img + mkfs.vfat ./sonic-installer.img mkfs.fat 4.2 (2021-01-31) ++ mktemp -d + tmpdir=/tmp/tmp.TqdDSc00Cn + mount -o loop ./sonic-installer.img /tmp/tmp.TqdDSc00Cn + cp target/sonic-vs.bin /tmp/tmp.TqdDSc00Cn/onie-installer.bin cp: error writing '/tmp/tmp.TqdDSc00Cn/onie-installer.bin': No space left on device [ FAIL LOG END ] [ target/sonic-vs.img.gz ] ``` #### How I did it Increase the size from 2048M to 4096M. Why not increase to 16G like qcow2 image? The qcow2 supports the sparse disk, although a big disk size allocated, but it will not consume the real disk size. The falocate does not support the sparse disk. We do not want to allocate a very big disk, but no use at all. It will require more space to build. * Update sensor names for msn4600c for the 5.10 kernel (sonic-net#11491) * Update sensor names for msn4600c for the 5.10 kernel Looks like a sensor was removed in the 5.10 kernel for the tps53679 sensor, so the names/indexing has changed. Related to sonic-net/sonic-mgmt#4513. Signed-off-by: Saikrishna Arcot <sarcot@microsoft.com> * Update sensors file Signed-off-by: Saikrishna Arcot <sarcot@microsoft.com> Signed-off-by: Saikrishna Arcot <sarcot@microsoft.com> * Fix error handling when failing to install a deb package (sonic-net#11846) The current error handling code for when a deb package fails to be installed currently has a chain of commands linked together by && and ends with `exit 1`. The assumption is that the commands would succeed, and the last `exit 1` would end it with a non-zero return code, thus fully failing the target and causing the build to stop because of bash's -e flag. However, if one of the commands prior to `exit 1` returns a non-zero return code, then bash won't actually treat it as a terminating error. From bash's man page: ``` -e Exit immediately if a pipeline (which may consist of a single simple command), a list, or a compound command (see SHELL GRAMMAR above), exits with a non-zero status. The shell does not exit if the command that fails is part of the command list immediately following a while or until keyword, part of the test following the if or elif reserved words, part of any command executed in a && or || list except the command following the final && or ||, any command in a pipeline but the last, or if the command's return value is being inverted with !. If a compound command other than a subshell returns a non-zero status because a command failed while -e was being ignored, the shell does not exit. ``` The part `part of any command executed in a && or || list except the command following the final && or ||` says that if the failing command is not the `exit 1` that we have at the end, then bash doesn't treat it as an error and exit immediately. Additionally, since this is a compound command, but isn't in a subshell (subshell are marked by `(` and `)`, whereas `{` and `}` just tells bash to run the commands in the current environment), bash doesn't exist. The result of this is that in the deb-install target, if a package installation fails, it may be infinitely stuck in that while-loop. There are two fixes for this: change to using a subshell, or use `;` instead of `&&`. Using a subshell would, I think, require exporting any shell variables used in the subshell, so I chose to change the `&&` to `;`. In addition, at the start of the subshell, `set +e` is added in, which removes the exit-on-error handling of bash. This makes sure that all commands are run (the output of which may help for debugging) and that it still exits with 1, which will then fully fail the target. Signed-off-by: Saikrishna Arcot <sarcot@microsoft.com> Signed-off-by: Saikrishna Arcot <sarcot@microsoft.com> * Fix vs check install login timeout issue (sonic-net#11727) Why I did it Fix a build not stable issue: sonic-net#11620 The vs vm has started successfully, but failed to wait for the message "sonic login:". There were 55 builds failed caused by the issue in the last 30 days. AzurePipelineBuildLogs | where startTime > ago(30d) | where type =~ "task" | where result =~ "failed" | where name =~ "Build sonic image" | where content contains "Timeout exceeded" | where content contains "re.compile('sonic login:')" | project-away content | extend branchName=case(reason=~"pullRequest", tostring(todynamic(parameters)['system.pullRequest.targetBranch']), replace("refs/heads/", "", sourceBranch)) | summarize FailedCount=dcount(buildId) by branchName branchName FailedCount master 37 202012 9 202106 4 202111 2 202205 1 201911 1 It is caused by the login message mixed with the output message of the /etc/rc.local, one of the examples as below: (see the message rc.local[307]: sonic+ onie_disco_subnet=255.255.255.0 login: ) The check_install.py was waiting for the message "sonic login:", and Linux console was waiting for the username input (the login message has already printed in the console). https://dev.azure.com/mssonic/build/_build/results?buildId=123294&view=logs&j=cef3d8a9-152e-5193-620b-567dc18af272&t=359769c4-8b5e-5976-a793-85da132e0a6f 2022-07-17T15:00:58.9198877Z [ 25.493855] rc.local[307]: + onie_disco_opt53=05 2022-07-17T15:00:58.9199330Z [ 25.595054] rc.local[307]: + onie_disco_router=10.0.2.2 2022-07-17T15:00:58.9199781Z [ 25.699409] rc.local[307]: + onie_disco_serverid=10.0.2.2 2022-07-17T15:00:58.9200252Z [ 25.789891] rc.local[307]: + onie_disco_siaddr=10.0.2.2 2022-07-17T15:00:58.9200622Z [ 25.880920] 2022-07-17T15:00:58.9200745Z 2022-07-17T15:00:58.9201019Z Debian GNU/Linux 10 sonic ttyS0 2022-07-17T15:00:58.9201201Z 2022-07-17T15:00:58.9201542Z rc.local[307]: sonic+ onie_disco_subnet=255.255.255.0 login: 2022-07-17T15:00:58.9202309Z [ 26.079767] rc.local[307]: + onie_exec_url=file://dev/vdb/onie-installer.bin How I did it Input a newline when finished to run the script /etc/rc.local. If entering a newline, the message "sonic login:" will prompt again. * [ci] Fix bug involved by PR 11810 which affect official build pipeline (sonic-net#11891) Why I did it Fix the official build not triggered correctly issue, caused by the azp template path not existing. How I did it Change the azp template path. * DellEMC: Z9332f - Graceful platform reboot (sonic-net#10240) Why I did it To gracefully unmount filesystems and stop containers while performing a cold reboot. Unmount ONIE-BOOT if mounted during fast/soft/warm reboot How I did it Override systemd-reboot service to perform a cold reboot. Unmount ONIE-BOOT if mounted using fast/soft/warm-reboot plugins. How to verify it On reboot, verify that the container stop and filesystem unmount services have completed execution before the platform reboot. * [Nokia][Nokia-IXR7250E-36x100G & Nokia-IXR7250E-36x400G] Update BCM (sonic-net#11577) config to support ERSPAN egress mirror and also set flag to preserve ECN * Align API get_device_runtime_metadata() for python version < 3.9 (sonic-net#11900) Why I did it: API get_device_runtime_metadata() added by sonic-net#11795 uses merge operator for dict but that is supported only for python version >=3.9. This API will be be used by scrips eg:hostcfgd which is still build for buster which does not have python 3.9 support. * [Arista7050cx3] TD3 SKU changes for pg headroom value after interop testing with cisco 8102 (sonic-net#11901) Why I did it After PFC interop testing between 8102 and 7050cx3, data packet losses were observed on the Rx ports of the 7050cx3 (inflow from 8102) during testing. This was primarily due to the slower response times to react to PFC pause packets for the 8102, when receiving such frames from neighboring devices. To solve for the packet drops, the 7050cx3 pg headroom size has to be increased to 160kB. How I did it Modified the xoff threshold value to 160kB in the pg_profile file to allow for the buffer manager to read that value when building the image, and configuring the device How to verify it run "mmuconfig -l" once image is built Signed-off-by: dojha <devojha@microsoft.com> * Add peer review comments on bgp * Add peer review changes + spacing * Add changes to events-swss * Add peer review changes in pmon swss * Add review changes dhcp-relay * Add peer review changes to host * Add changes to severity, leafref * Remove unused grouping * Remove redis generic Signed-off-by: Saikrishna Arcot <sarcot@microsoft.com> Signed-off-by: dojha <devojha@microsoft.com> Co-authored-by: Samuel Angebault <staphylo@arista.com> Co-authored-by: Junhua Zhai <junhua.zhai@outlook.com> Co-authored-by: Liu Shilong <shilongliu@microsoft.com> Co-authored-by: abdosi <58047199+abdosi@users.noreply.github.com> Co-authored-by: xumia <59720581+xumia@users.noreply.github.com> Co-authored-by: Saikrishna Arcot <sarcot@microsoft.com> Co-authored-by: Arun Saravanan Balachandran <52521751+ArunSaravananBalachandran@users.noreply.github.com> Co-authored-by: saksarav-nokia <sakthivadivu.saravanaraj@nokia.com> Co-authored-by: Dev Ojha <47282568+developfast@users.noreply.github.com>
richardyu-ms
pushed a commit
to richardyu-ms/sonic-buildimage
that referenced
this pull request
Nov 25, 2022
This change is already included in 202012 branch: https://github.com/sonic-net/sonic-buildimage/blob/202012/device/arista/x86_64-arista_7050cx3_32s/Arista-7050CX3-32S-C32/BALANCED/pg_profile_lookup.ini |
Sign up for free
to join this conversation on GitHub.
Already have an account?
Sign in to comment
Add this suggestion to a batch that can be applied as a single commit.
This suggestion is invalid because no changes were made to the code.
Suggestions cannot be applied while the pull request is closed.
Suggestions cannot be applied while viewing a subset of changes.
Only one suggestion per line can be applied in a batch.
Add this suggestion to a batch that can be applied as a single commit.
Applying suggestions on deleted lines is not supported.
You must change the existing code in this line in order to create a valid suggestion.
Outdated suggestions cannot be applied.
This suggestion has been applied or marked resolved.
Suggestions cannot be applied from pending reviews.
Suggestions cannot be applied on multi-line comments.
Suggestions cannot be applied while the pull request is queued to merge.
Suggestion cannot be applied right now. Please check back later.
Arista7050cx3 TD3 SKU changes for pg headroom value after interop testing with cisco 8102
Signed-off-by: dojha devojha@microsoft.com
Why I did it
After PFC interop testing between 8102 and 7050cx3, data packet losses were observed on the Rx ports of the 7050cx3 (inflow from 8102) during testing. This was primarily due to the slower response times to react to PFC pause packets for the 8102, when receiving such frames from neighboring devices. To solve for the packet drops, the 7050cx3 pg headroom size has to be increased to 160kB.
How I did it
Modified the xoff threshold value to 160kB in the pg_profile file to allow for the buffer manager to read that value when building the image, and configuring the device
How to verify it
run "mmuconfig -l" once image is built
Which release branch to backport (provide reason below if selected)
Description for the changelog
Changed pg headroom valuesLink to config_db schema for YANG module changes